Water mist module - 30 - EM/R INEI

Information center

+375 (29) 668-22-77

Working hours: Mo-Fr: 8:15-17:00

CREATING FOR LIFE

Description
Code
Models
Water mist module - 30 - EM/R INEI
241-02
with electromagnetic and manual start device
  • 4 years warranty
Main technical data and characteristics
Bottle capacity for the firefighting agent (FFA) min, l
32
Charge volume, l
30
Operational pressure in the FFA container at +20 °C, MPa
1,0-1,4
Starting bottle capacity, min, l: - liquefied carbon dioxide (CO2)
5
Propellant gas weight, min, kg
3,5
Operational pressure in the starting bottle at +20 °C? MPa (rated) - liquefied carbon dioxide (CO2)
5,8
FFA average discharge, l/s
0,75
Activation delay time, max, s
2
Useful time, min, s
40
Number of activations possible, min, No.
10
Firefighting system dimensions (w/o the distribution network):
- height (H), max, mm;
520
-width (L), max, mm
850
Firefighting system weight (w/o the distribution network), max, kg:
- fully rigged (charged);
45
- w/o FFA charge (with a charged propellant gas container)
21
Protected area for class A fires, no more than m²
- at h≤4.0 m
20
- at h≤6.0 m
15
- at h≤9.0 m
-
Protected area for class B fires, no more than m²
- at h≤4.0 m
15
- at h≤6.0 m
12
- at h≤9.0 m
-
Number of nozzles
8
Operating temperature range, ˚С
summer version
from +5 to+50
Starting cylinders INEI, used for aggregated execution (with a centralized gas source)
MGPU-150-50-12 INEI
up to 5
MGPU-150-67-12 INEI
up to 6
MGPU-150-100-12 INEI
up to 10
Connecting thread spray nozzle
G1/2" internal
ID code:
MUPTV-30-EM/R INEI (Summer version)
241-02
The start of the MUPTV INEI marked EM / R is carried out by actuating the electromagnet (solenoid) of the start cylinder built into the valve. Also, the activation of the installation can be carried out by acting on the handle of the manual start of the valve.
Загрузка...