Description
Code
Models
Water mist module - 90 - EM/R-Ex INEI
241-19
with electromagnetic and manual start device, explosion-proof version
  • 4 years warranty
Main technical data and characteristics
Bottle capacity for the firefighting agent (FFA) min, l
90
Charge volume, l
90
Operational pressure in the FFA container at +20 °C, MPa
1,0-1,4
Starting bottle capacity, min, l: - liquefied carbon dioxide (CO2)
10
Propellant gas weight, min, kg
10
Operational pressure in the starting bottle at +20 °C? MPa (rated) - liquefied carbon dioxide (CO2)
5,8
FFA average discharge, l/s
3
Activation delay time, max, s
2
Useful time, min, s
30
Number of activations possible, min, No.
10
Parameters of automatic electric start signals:
voltage, within, V
24
direct current, not less than, A
0.5
Firefighting system dimensions (w/o the distribution network):
- height (H), max, mm;
600
width (L), max, mm
1450
Firefighting system weight (w/o the distribution network), max, kg:
- fully rigged (charged);
190
- w/o FFA charge (with a charged propellant gas container)
100
Protected area for class A fires, no more than m²
- at h≤4.0 m
60
- at h≤6.0 m
45
- at h≤9.0 m
36
Protected area for class B fires, no more than m²
- at h≤4.0 m
45
- at h≤6.0 m
36
- at h≤9.0 m
27
Number of nozzles
32
Operating temperature range, ˚С (summer version)
from +5 to+50
Starting cylinders INEI, used for aggregated execution (with a centralized gas source)
MGPU-150-50-12 INEI
MGPU-150-67-12 INEI
up to 3
MGPU-150-100-12 INEI
up to 5
Connecting thread spray nozzle
G1/2" internal
ID code:
MUPTV-90-EM/R-Ex INEI (Summer version)
241-19
The systems are intended to protect premises and outdoor systems located in explosion hazard zones of class 1 and 2 according to GOST IEC 60079-10-1-2011, where the appearance of an explosive atmosphere in the form of a mixture of flammable gases with air is probable under normal operating conditions in accordance with the assigned explosion protection marking.

The device is not applicable to fire equipment installed in underground mine workings of mines and deposits and their above-ground buildings dangerous due to mine gas and/or dust.

The systems are intended for extinguishing fires of classes: A (solids combustibles), B (flammable liquids) and E (electrical installations with voltage up to 1000 V) according to GOST 27331 in enclosed and semi-enclosed spaces of premises of various classes according to functional fire hazard: industrial, storage, administrative, archive, storages of museum values and exhibitions, as well as for protection of technological and other equipment. The systems are used to protect both individual fire-hazard zones and the entire volume of protected premises.

The systems are not applicable for extinguishing chemically active substances that react with water (alkali metals, aluminum - organic compounds, etc.).