Information center

+375 (29) 667-22-77

Working hours: Mo-Fr: 8:00-17:00

CREATING FOR LIFE

Code: 231-09
CO2 Carbon dioxide module 150-100-12 INEI

Main technical data and characteristics
CO2, lt
100±5
Operational pressure of the unit, MPa (bar)
14,7 (150)
Test pressure of the unit, MPa
22,5
Actuating pressure of the diaphragm safety device, MPa
- minimum
18,5
- maximum
20,0
Unit dimensions w/o actuation mechanisms, mm, max
- diameter D
316
- height
1638
- with protective hood installed
1695
Height to outlet center, mm
1577+3
Connecting thread of the output fitting
W21,8x1/14 DIN477
Nominal bore of the lock and release device/dip tube, NB, mm
12/12
Unit weight w/o charge, kg
105±7,5
Discharge time for 95% of the GAFF volume, measured by weight, s, max
60
GAFF residue in the bottle, kg, max
0,5
DC voltage of the electromagnetic actuator, V
24
Actuating current of the electromagnetic actuator, A
0,5
Bottle inspection frequency
Once every 10 years