Portable CO2 Fire Extinguisher INEI 5 kg BCE (55B C E up to 10kVt) cylinder 7l 200/300 Bar

Information center

+375 (29) 668-22-77

Working hours: Mo-Fr: 8:15-17:00

CREATING FOR LIFE

Description
Code
Models by GOST15150/ ISO12944
Portable CO2 Fire Extinguisher INEI 5 kg BCE (55B C E)
112-04
O2/C2
Portable CO2 Fire Extinguisher INEI 5 kg BCE-OM2 (55B C E)
112-203
OM2/C4-H
Main technical data and characteristics
Rank of standardized fire source (fire extinguishing capability) for class B
55В
Fire extinguishing capability for class C
available (not measured)
Fire extinguishing capability for class E
up to 10000V
Operating temperature range, °C
from -40 to +50
Gross weight, kg
21,8
Dimensions(length, cylinder diameter), mm., not more
800x145
Mass of fire extinguishing agent, kg
5+0,25
Cylinder volume, l
7,2
Cylinder design
Seamless
Cylinder service life, years
15
Fire extinguisher service life, years
15
Branded factory repair work
available (factory warranty for factory repair work is 5 years)
Minimum recharge cycle
every 5 years
Warranty, years
4 (twice as much as the standard)
Recommended transport brackets
KTR-OU-5 (code 122-53), KTH-5+ (code 121-153), KTRR (code 121-106)
WHAT YOU SHOULD PAY ATTENTION TO:
     Ability to extinguish electrical equipment under voltage: up to 10,000 volts.
    Connecting thread of the cylinder and valve: W27.8.
    The sprayer is marked with an indication of the manufacturer and the standard size of the fire extinguisher for use with which it is intended.                                
    Sprayer length: not less than 0.75 m.
    The mass of the fire extinguisher without charge is indicated on the valve.
    The cylinder is marked in the form of clear and indelible inscriptions: Trademark of the manufacturer; Name of the cylinder, Serial number of the cylinder; Month, year of manufacture of the cylinder and year of its re-examination;  Working and test pressure of the cylinder; Mass and volume of the cylinder.
    Also, the fire extinguisher cylinder is marked with the EAC mark.
    The cylinder has a certificate for compliance with TR CU 032/2013.
ОУ-5-ВСЕ ИНЕЙ