Description
Code
MGPH 18-2,5-12 INEI
236-01
with electrical ignition

- 4 YEARS WARRANTY
- RECHARGE IN 10 YEARS
- TR CU CERTIFIED
Main technical data and characteristics
Unit cylinder capacity, l
2,5 ±0,125
Max working pressure, MPa
1.8
The activation pressure of the safety device, MPa
- minimal
2,4
- maximum
2,8
Time to achieve 95% mass discharge of the fire extinguishing agent (FEA), sec, not more
10
The minimum number of module activations during the service life
10
Unit dimensions, mm
- diameter
180±5
- height
166±5
Module weight without the fire extinguishing agent (FEA), kg, not exceeding
1.5
Mass of the fire extinguishing agent (HFC-227) not exceeding, kg
2.75
Remaining fire extinguishing agent (HFC-227) in the cylinder, kg, not exceeding
0.1
Resistance of the ignition device, Om
6...12
Safe current for testing the electrical ignition circuit
0.050 Amps for a duration of 5.0 minutes
The maximum constant current for monitoring the electrical ignition circuit during the service life, A
0,005
The constant current for triggering the electrical ignition circuit
0.20±0.01 Amperes with a pulse duration of 0.020±0.001 sec
Activation voltage of the module, V
3...24